henhaobio
Sign in

bioRxivMicrobiology

Presence of Legionella spp. in cooling towers: the role of microbial diversity, Pseudomonas, and continuous chlorine application.

K. Paranjape, E. Bedard, L. G. Whyte, J. Ronholm, M. Prevost, S. P. Faucher

PDFDOIPreprint

Abstract

Legionnaires Disease (LD) is a severe pneumonia caused by Legionella pneumophila. Cooling towers are the main source of L. pneumophila during large outbreaks. Colonization, survival, and proliferation of L. pneumophila in cooling towers are necessary for outbreaks to occur. These steps are affected by chemical and physical parameters of the cooling tower environment. We hypothesize that the bacterial community residing in the cooling tower could also affect the presence of L. pneumophila. A 16S rRNA targeted amplicon sequencing approach was used to study the bacterial community of cooling towers and its relationship with the Legionella spp. and L. pneumophila communities. The results indicated that the water source shaped the bacterial community of cooling towers. Several taxa were enriched and positively correlated with Legionella spp. and L. pneumophila. In contrast, Pseudomonas showed a strong negative correlation with Legionella spp. and several other genera. Most importantly, continuous chlorine application reduced microbial diversity and promoted the presence of Pseudomonas creating a non-permissive environment for Legionella spp. This suggests that disinfection strategies as well as the resident microbial population influences the ability of Legionella spp. to colonize cooling towers.

Reproducibility ledger

Nobody has reported trying to reproduce this paper yet. Did you replicate an experiment or run the code? Your report saves the next lab a week.

Sign in to file a reproducibility report.

Similarity Map
SelectedSame fieldCross-field
THISPaniagua '19Faucher '22Smeltz '25Scaturro '22Saoud '20Bedard '21
82% semantic matchMicrobiology
A. Torres Paniagua, K. Paranjape, M. Hu+2 more·bioRxiv·Dec 12, 2019